Back to Viessmann products

Vitocal 200-A ie launch reference

Launch documentation · Provisional · Reference only

Viessmann Vitocal 200-A ie

R290 monoblock range, sizes 06 / 08 / 10 / 12, with distinct V004 protective-heater and V005 comfort-heater versions. These records are not selectable equipment and do not change your current design.

Manufacturer notice — 6260605, p.93

These specifications are provisional. The specifications at the time of delivery of the series product are definitive.

Final specifications, design-condition performance data and the exact system arrangement require manufacturer verification before this range can be selected or quoted. Automatic recommendations, pricing, customer proposals and installation drawings are disabled for this range.

Size 06

5.2 kW

Rated output at A−7/W55 · EN 14511

At A−7/W35
5.46 kW
Sound power: ErP / maximum
48 / 56 dB(A)
R290 charge
1 kg
SCOP / price
Not verified / Not quoted

Reference only — cannot apply to design

Size 08

7.0 kW

Rated output at A−7/W55 · EN 14511

At A−7/W35
6.8 kW
Sound power: ErP / maximum
53 / 59 dB(A)
R290 charge
1 kg
SCOP / price
Not verified / Not quoted

Reference only — cannot apply to design

Size 10

8.4 kW

Rated output at A−7/W55 · EN 14511

At A−7/W35
8.7 kW
Sound power: ErP / maximum
54 / 61 dB(A)
R290 charge
1.4 kg
SCOP / price
Not verified / Not quoted

Reference only — cannot apply to design

Size 12

9.4 kW

Rated output at A−7/W55 · EN 14511

At A−7/W35
9.7 kW
Sound power: ErP / maximum
55 / 61 dB(A)
R290 charge
1.4 kg
SCOP / price
Not verified / Not quoted

Reference only — cannot apply to design

Published points are at −7°C outdoor air, not your property’s design temperature. They are not interpolated into performance curves. Sound figures are sound power, not sound pressure at a neighbour’s window. Source: 6260605 pp.93–95.

Published specification details

Maximum flow 75°C; maximum at −10°C outdoor air 70°C. Heating refrigerant-circuit switch-on -20°C / switch-off -25°C. Maximum cooling air inlet 45°C. These are limits, not guaranteed output or efficiency at every condition.

ErP average-climate seasonal efficiency ηs is not SCOP. Dimensions are length × width × height.
Sizeηs W35 / W55Max currentDimensions mmWeight
06202% / 151%14 A530 × 1140 × 80893 kg
08202% / 153%14 A530 × 1140 × 80893 kg
10208% / 155%16 A530 × 1140 × 1008118 kg
12204% / 155%20 A530 × 1140 × 1008118 kg

Outdoor-unit supply: 1/N/PE 230 V~/50 Hz. G 1 male thread — heating water flow/return. Maximum secondary-side operating pressure: 3 bar.

V005 heater supply is additional; outdoor-unit current alone is not total installation demand.

Sources and requirements before release
  • Final series-product specifications matched to the installed size and V004/V005 nameplate.
  • Manufacturer performance data over design outdoor/flow conditions, seasonal efficiency evidence and operating envelope.
  • Exact approved hydraulic schematic ID/revision, controller/IDU choice and variant-specific wiring.
  • Verified compatible accessories, part codes, quantities and actual supplier costs (ex VAT).
  • Controller/software-specific commissioning and handover review, including heater-setting discrepancy.

6260605 · Vitocal 200-A outdoor unit — installation and service · 104 pages

User-supplied launch edition; provisional

6261130 · IDU controller IW B1-V — installation and service · 88 pages

User-supplied launch edition

6260634 · Vitocal 200-A outdoor unit — connection and wiring diagram · 36 pages

User-supplied launch edition

The manufacturer’s schematic browser lists Vitocal 200-A ie arrangements. These have not been approved or imported into our automatic schematic engine. Regional applicability and exact IDU/variant must be checked.